8. Fault analysis and rectification
The device terminal strip is live during operation!!
Before working on the device disconnect it from the mains!!
flashing green LED
(1Hz):
low voltage
flashing red LED for
4..16s
(1 Hz / DIP-switch)
followed by permanent
red LED
insulation electrode
stained
permanent red and
yellow LEDs
restart controller by
disconnecting from and
reconnecting to power
supply;
change controller
permanent red LED
together with flashing
(1Hz) yellow LED
fault in measuring
cable
(short circuit or cable
break)
Check cap 4.2, too