Nemo 96HD+
07/17 10783482 WEB E cod.MF9602.A
10
2.0 Password 2001
Press key
Load password 2001 and confirm
moves the cursor
increases/decreases the loaded value
↵ confirms
2.1 External CT ratio
Ct = External primary/secondary (ex. CT 800/5A Ct = 160)
Selection in the field 1...9999 (max. primary current CT 50kA/5A – 10kA/1A)
moves the cursor
increases/decreases the loaded value
↵ confirms
External VT ratio
Vt = External primary/secondary VT ratio (ex. VT 600/100V Vt = 6)
Selection in the field 1,00...3000,0 (max. primary voltage VT 150kV)
For voltage direct connection (without external VT) load Vt =1,00
By modifying the Ct and/or Vt ratios, the KWH meters are automatically
reset.
moves the cursor
increases/decreases the loaded value
↵ confirms