PROTOCOL COMMUNICATION
PT10789220
pag. 19/22
Current ratio (KTI) (block 7.6)
The current transformer ratio is the ratio between the rated primary value and the rated secondary value.
For example, if a CT primary/secondary ratio is 100/5, the value to be set in NEMO96HD is 20 and this is also the value
given on the remote line.
Format : WORD
Measurement unit : //
Voltage ratio (KTU) (block 7.7)
The voltage transformer ratio is the ratio between the rated primary value and the rated secondary value.
For example, if a VT primary/secondary is 380/100, the value to be set in NEMO96HD is 3.8
For the TVs, the first decimal of the ratio is kept and so the value given on the remote line is multiplied by 10, in this case
38.
Format : WORD
Measurement unit : //
Ratio KTV * KTU (block 7.8)
Format : DWORD
Measurement unit : //