PROTOCOL COMMUNICATION
PT10789220
pag. 14/22
7. Variables description
BLOCK 1
Phase voltage 1 / 2 / 3 (block 1.1 / 1.2 / 1.3)
This is the phase to neutral voltage. This measure is available also in the 2 systems connection (Aron).
Format : DWORD
Measurement unit : mV
Example : 100V => 100000 mV => 0x00 01 86 a0
Phase current 1 / 2 / 3 (block 1.4 / 1.5 / 1.6)
Format : DWORD
Measurement unit : mA
Example : 5.4A => 5400 mA => 0x00 00 15 18
Neutral current (block 1.7)
The neutral current is the real time sum of the 3 single phase currents.
Format : DWORD
Measurement unit : mA
Example : 5.4A => 5400 mA => 0x00 00 15 18