TROUBLE SHOOTING RX
RX
RX
hexadecimal Error description details solution
05-B7
Error during EEPROM reading The EEPROM memory cannot be
correctly read by the micro
s
Check if the EEPROM is
correctly plug in its socket
correctly
read
by
the
micro s
.
correctly
plug
in
its
socket
06
Error detected during Safety-Stop
monitoring
The S-STOP status does not match its
command signal
Check the S-STOP relay. If
necessary replace it
08
08
Error detected during E-STOP
monitoring
The E-STOP status does not match its
command signal
Check the E-STOP relay. If
necessary replace it
0A
10
SAFETY-STOP detected closed
during START phase
The S-STOP status does not match its
command signal
Check the S-STOP relay. If
necessary replace it
Error detected on the volta
g
e The volta
g
e comin
g
out from the
The power source might ce
instable with frequent drops out.
Otherwise the board Graetz
11
g
value of the logical board power
supply during receiver start up.
gg
switching transformer is no valid (too low
or too high)
Otherwise
the
board
Graetz
bridge is defective (change the
Graetz Bridge or the complete
mother board)
The dip-switches are not set according
19
14
Wrong dip switch configuration
(only for WAVE)
to an allowed configuration, so, the
software does not allow the receiver to
operate.
Check out the technical
enclosures.