3.12 TECHNICAL SPECIFICATIONS.
6 8 12 16
Nominal data for low temperature applications *
Nominal output kW 5.76 7.16 11.86 15.00
Absorption kW 1.35 1.80 3.00 3.57
COP kW/kW 4.28 3.97 3.95 4.20
Nominal output kW 7.04 7.84 13.54 16.00
Absorption kW 1.90 1.96 3.70 4.20
EER kW/kW 3.70 3.99 3.66 3.81
Nominal output for average temperature applications **
Nominal output kW 5.76 7.36 12.91 14.50
Absorption kW 1.89 2.31 4.26 4.39
COP kW/kW 3.05 3.19 3.03 3.30
Nominal output kW 4.73 5.84 10.24 13.00
Absorption kW 1.58 1.96 3.46 4.47
EER kW/kW 3.00 2.98 2.96 2.91
Nominal output for high temperature applications **
Nominal output kW 5.43 7.25 10.87 12.17
Absorption kW 1.95 2.58 4.05 4.08
COP kW/kW 2.77 2.81 2.68 2.98
Maximum input kW 2 2.7 3.85 6.5
Weight kg 61 69 104 116
Coolant gas R-410A R-410A R-410A R-410A
Quantity of coolant kg 1.35 1.81 2.45 3.385
Hydraulic circuit
Water content l 1 1.2 2.5 2.5
Expansion vessel volume l 2 2 3 3
Hydraulic circuit maximum pressure kPa 300 300 300 300
Hydraulic connection in 1 1 1 1
* Central heating mode status: heat exchanger water inlet/remains at 30 °C/35 °C, outdoor air temperature 7 °C db/6 °C wb. Performance in compliance
with EN 14511.
Cooling mode status: heat exchanger water inlet/remains at 23 °C/18 °C, outdoor air temperature 35 °C. Performance in compliance with EN 14511.
** Central heating mode status: heat exchanger water inlet/remains at 40 °C/45 °C, outdoor air temperature 7 °C db/6 °C wb.
Cooling mode status: heat exchanger water inlet/remains at 12 °C/7 °C, outdoor air temperature 35 °C. Performance in compliance with EN 14511.
*** Central heating mode status: inlet/remains at 47 °C/55 °C, outdoor air temperature 7 °C db/6 °C wb. Performance in compliance with EN 14511.

Other manuals for Immergas AUDAX TOP 6 ErP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Immergas AUDAX TOP 6 ErP and is the answer not in the manual?

Immergas AUDAX TOP 6 ErP Specifications

General IconGeneral
BrandImmergas
ModelAUDAX TOP 6 ErP
CategoryHeat Pump
LanguageEnglish

Related product manuals