Replace data point pair #n with a
new data pair x.xxxx,y.yyyy
Will possibly re-number entries in the
table (X=Degrees, Y= Conv. Value)
Delete data point pair #n from
the N.L. Conversion Table
Will re-number entries in the table
Add a learned a data point pair
to the Non-Linear Conversion
Table
Will possibly re-number entries in the
table (Learned Degrees, Y= Conv. Value)
n= an integer from 2 to 100
n= a floating-point number, 5 digits max,
average number of degrees between taps
Set number of neutral taps
n= an integer from 0 to 9
Set neutral start tap number
n= an integer, any valid tap number
n= an integer, any valid tap number
Set high relay tap number
n= an integer, any valid tap number
n= an integer, any valid tap number
Load present tap pos. into memory
Must be done for SETTAP to take effect
Enables the display of “r” (raised)
and “L” (lowered) tap numbers
“ON” or “OFF” When enabled causes the
display to show “r” and “L” in function
modes 20 and 21 only
Enter analog calibration mode, the
1250 analog output will be forced
to Low / Mid / High signal output
Press the space bar to toggle between
Low / Mid / High analog output. Press the
enter key to stop calibration
Turns on all display segments
Press the enter key to stop the LED test
Turns on one relay at a time for
testing
Press the space bar to toggle between
Low relay and High relay. Press Enter to
Exit Test
Self-calibrates the input circuitry
Outputs “Pass” or “Fail” calibration result
Enables the display blanking
feature
“ON” or “OFF” When enabled causes the
display to go blank after 60 sec.
Enables the automatic reset after
an “FA25” error
“ON” or “OFF” When enabled, will
automatically return to normal run mode
after input signal returns to normal range
Manually resets the “FA25” error.
Set serial RS-232
communication mode
0=Serial Disabled, 1=Data Logger Mode,
2=Polled Mode, 3=Sampled Mode,
4=Serial Command Mode, 5= Reserved,
6=RS485 Mode, 7=Remote Display Driver
Set comm. port settings: baud
rate, word length, parity, stop
bits, and address
b= 2400, 4800, 9600, 14400, 19200, 28800,
38400, 57600, 76800 baud
w= 7 or 8-bit word
p= n, E, O
s= 1 or 2 stop bits
a= 0 to 255
Displays Status of program
disable input
“1” = Numeric menu or
“2” = Alpha-numeric menu
Lists all available commands
All commands will be listed with syntax