1
Page 1 - 4 Tank Sentinel Setup Programming Guide
S
YSTEM
Menu (C
ONTINUED
...
FROM
PREVIOUS
PAG E
)
SENTINEL
(after hours theft monitoring / tank leak detection)
SENTINEL MODE
MODE
SENTINEL MODE
OFF
Use
UP/DOWN
keys to choose mode.
SCHEDULED
Press
ENTER
to accept this data.
Select SCHEDULED to enable Sentinel Mode —
START TIM
SENTINEL START TIME
00.00.00
up to 23.59.59
END TIME
SENTINEL END TIME
00.00.00
up to 23.59.59
DEL DELAY
(delay tank delivery reports by minutes)
DELIVERY DELAY
15
(minutes) 1 to 240 minute input range.
Press
ENTER
to accept this data.
REP DELIV
REPORT DELIVERIES
Use
UP/DOWN
keys to choose.
Press
ENTER
to accept this data.
ENABLED
(enabled = yes, report deliveries)
DISABLED
(disabled = no, don’t report deliveries)
REP ALARM
REPORT ALARMS
Use
UP/DOWN
keys to choose.
Press
ENTER
to accept this data.
ENABLED
(enabled = yes, report alarms)
DISABLED
disabled = no, don’t report alarms)
REP LEAK
REPORT LEAK TESTS
Use
UP/DOWN
keys to choose.
Press
ENTER
to accept this data.
ENABLED
(enabled = yes, report leak test results)
DISABLED
(disabled = no don’t report leak test results)
REP SCALD
(Appears only if an S is present in the TS Part
REPORT SCALD TEST
Number (press CHECK and M4 to view OPTIONS)
Use
UP/DOWN
keys to choose.
Press
ENTER
to accept this data.
DISABLED
(disabled = no, don’t report SCALD leak tests)
ENABLED
(enabled = yes, report SCALD leak tests)
Input
time in 24 hour format:
00.00.00 = midnight
22.00.00 = 10:00:00 pm
+ 12
(add 12 hours to pm times
from 1 pm to 11:59 pm
)
02.05.00 = 2:05:00 am

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Incon task sentinel TS-504 and is the answer not in the manual?

Incon task sentinel TS-504 Specifications

General IconGeneral
BrandIncon
Modeltask sentinel TS-504
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals