REFRIGERAZIONE MOBILE - FRIGOBAR
ISO 9002 certified
TB 15-18
TB15-18_00_03-2012 17
ENGLISH
DEgREES fAhRENhEIT/CENTIgRADE
To set the temperature unit of measurement to degrees
Fahrenheit or Centigrade, activate symbols F or C
OvER - COOLINg
The Over - Cooling function, described above, is set
by activating symbols O C.
fAULTS
Any operation faults will be displayed after 90 seconds and will be presented on the display with the
following codes:
1 The thermostat has short-circuited or is not correctly connected to the control unit: R6
2 The compressor is blocked: R3
3 The ventilator is sending the control unit a value which exceeds 0.6A: R2
4 The cooling system holds too much gas and the compressor is not able to operate
at the minimum number of revolutions/rpm:
R4
5 The ambient temperature is too high: R5
6 Insufcient voltage (Voltage below the cut-out value): LO
7 No communication between the display and control unit, a scrolling horizontal
line appears on the DISPLAY for a few seconds, the refrigerator turns itself off.
-