• Mode B - PME as CPC with trip on L-N voltage measurement. No reference
electrode. For installations where an Earth Rod is not possible and/or there are
no simultaneous contact or touch voltage risks present. Consideration should
be given to nuisance trips where the line to neutral voltage may regularly exceed
253v, especially where local renewables are present, Mode A is less sensitive
to nuisance tripping.