18 – Inepro Metering – PRO Series
7.1 Errors / Diagnostics display
The meter is equipped with a display field that shows errors and diagnostics. It consists of the
character S followed by 2 + 3 digits. The meaning of each digit is as follows:
First digit: Program status (0 fail / 1 passed)
Second digit: Eeprom status (0 fail / 1 passed)
Third digit: Phase A status (0 not available / 1 available)
Fourth digit: Phase B status (0 not available / 1 available)
Fifth digit: Phase C status (0 not available / 1 available)
If the first or second digit shows a 0 (zero); then please return the meter, as the meter is
malfunctioning.
If the third, fourth or fifth digit shows a 0 (zero); please check the wiring for power issues.
7.2 Technical support
For questions about one of our products please contact:
- Your local Inepro Metering distributor
- Email: support@ineprometering.com
www.ineprometering.com