EasyManua.ls Logo

Inepro PRO380-Mod - 7.1 Errors; Diagnostics display

Default Icon
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 – Inepro Metering – PRO Series
7.1 Errors / Diagnostics display
The meter is equipped with a display field that shows errors and diagnostics. It consists of the
character S followed by 2 + 3 digits. The meaning of each digit is as follows:
First digit: Program status (0 fail / 1 passed)
Second digit: Eeprom status (0 fail / 1 passed)
Third digit: Phase A status (0 not available / 1 available)
Fourth digit: Phase B status (0 not available / 1 available)
Fifth digit: Phase C status (0 not available / 1 available)
If the first or second digit shows a 0 (zero); then please return the meter, as the meter is
malfunctioning.
If the third, fourth or fifth digit shows a 0 (zero); please check the wiring for power issues.
7.2 Technical support
For questions about one of our products please contact:
- Your local Inepro Metering distributor
- Email: support@ineprometering.com
www.ineprometering.com