EasyManua.ls Logo

inform PDSP31010 - Page 58

inform PDSP31010
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
Voltage Range (Line-
Neutral) [V]*(1)
220 V /230V /240V ±%10
Frequency Range [Hz]
*(1)
47-53
Nominal Apparent
Power [kVA]
10
15
20
30
40
60
80
100
120
Nominal Current [A]
15
23
30
45
61
91
121
151
182
Transfer Duration [ms]
0
STATIC BY-PASS LINE @ 1PH OUTPUT UPS’S
Number of Phases
1P+N+PE
-
Voltage Range (Line-
Neutral) [V]*(1)
220 V /230V /240V ±%10
-
Frequency Range [Hz]
*(1)
47-53
-
Nominal Apparent
Power [kVA]
10
15
20
30
40
-
Nominal Current [A]
45
68
91
136
182
-
Transfer Duration [ms]
0
-
BATTERIES
Battery Type
Sealed lead acid, 12 V
Number of Batteries
2x31
Nominal Battery Voltage
[V]
2x372
Stored
energy time
@ nominal
load with
standard
internal
batteries*(2)
7Ah
14m
6m
4,5m
-
-
9 Ah
25m
10m
7m
2,5m
-
PHYSICAL
Dimensions (WxDxH)
(cm)
40 x 77 x 110
52 x 90 x 130
67 x 73 x 160
63 x 100 x 140
85 x 77 x 182
Weight (kg)
102
110
240
242
260
295
330
STANDARDS
Safety
IEC / EN / TSE 62040-1
Performance
IEC / EN / TSE 62040-3
EMC
IEC / EN / TSE 62040-2
Product Certification
CE

Related product manuals