Configuration manual
System Parameters 17
If you are configuring an “SMS” or “PSTN” type channel, the communication protocol will be requested:
•SIA-IP
•Contact ID
• Voice call
•SMS
The parameters made available in the contact programming section that follows vary according to the selected protocol.
Pressing the Actions button [D] on the communicator configuration screen will access the list of communication
operations set on the control panel. Selecting one of them and then pressing the Program button accesses the
configuration screen.
The “Type” parameter allows you to specify which events will trigger the action (alarm, fault, etc.).
Note: For the first two actions (alarm and system failure), the “Description” and “Type” fields are not editable.
The Associated contacts button accesses a screen that allows you to specify to which contacts the event
communication will be sent.
If the presence of the Previdia-C-DIAL communicator, set by means of the previously-mentioned option, is
different from the one the control panel detects, the appropriate icon inside the control panel configuration
screen will change status and appear in yellow
.
3.9 Configuring the extinction channel
The parameters of the extinction channel, for control- panels that provide one, can be accessed through the
control-panel programming section (paragraph 2.2), by simply tapping on the relevant icon on the
configuration screen.
The successive sections provide the various programmable parameters (refer to the extinction flowchart and the table of
extinction-terminal functions in the installation manual).
3.9.1 Extinction times
The following parameters can be set on the extinction-
channel configuration page:
• Automatic pre-extinction time: duration of pre-
extinction time, in seconds, when triggered by fire-
fighting devices connected to the control panel.
• Manual pre-extinction time: duration of pre-extinction
time, in seconds, when triggered by input devices
programmed for manual-extinction (refer to following
sections).
• Valve Pulse (option 4.21 “Control of flooding time” of EN
12094-1): duration of release time, in seconds.
Leaving the respective box [A] empty removes all time
limitations.
000
Pre-ext. Automatic
(sec)
Zones
000
Pre-ext. Manual
(sec)
Inputs
Valve Pulse
300 (sec)
Esc Set
Access
level:3
A
B
C