Function Code Table
MD380 User Manual
- 124 -
Function
Code
Parameter Name
Setting Range
Default Property
Group A0: Torque Control and Restricting Parameters
A0-00
Speed/Torque
control selection
0: Speed control
1: Torque control
0 ƾ
A0-01
Torque setting source in
torque control
0: Digital setting (A0-03)
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication reference
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
The value 100% of 1 to 7
corresponds to the setting of A0-
03.
0 ƾ
A0-03
Torque digital setting in
torque control
-200.0% to 200.0%
150.0% ƿ
A0-05
Forward maximum
frequency in torque control
0.00 Hz to maximum frequency
(F0-10)
50.00 Hz ƿ
A0-06
Reverse maximum
frequency in torque control
0.00 Hz to maximum frequency
(F0-10)
50.00 Hz ƿ
A0-07
Acceleration time in torque
control
0.00–65000s
0.00s ƿ
A0-08
Deceleration time in torque
control
0.00–65000s
0.00s ƿ