Description of Function Codes                                                                
MD380 User Manual                                                 
- 158 -
Function Code Parameter Name Setting Range Default
F3-01 Torque boost 0.0%–30%
Model 
dependent
F3-02
Cut-off frequency of 
torque boost
0.00 Hz to maximum 
frequency
50.00 Hz
To compensate the low frequency torque characteristics of V/F control, you can boost the 
output voltage of the AC drive at low frequency by modifying F3-01.
If the torque boost is set to too large, the motor may overheat, and the AC drive may suffer 
overcurrent. 
,IWKHORDGLVODUJHDQGWKHPRWRUVWDUWXSWRUTXHLVLQVXI¿FLHQWLQFUHDVHWKHYDOXHRI)
If the load is small, decrease the value of F3-01. If it is set to 0.0, the AC drive performs 
automatic torque boost. In this case, the AC drive automatically calculates the torque boost 
value based on motor parameters including the stator resistance.
F3-02 specifies the frequency under which torque boost is valid. Torque boost becomes 
LQYDOLGZKHQWKLVIUHTXHQF\LVH[FHHGHGDVVKRZQLQWKHIROORZLQJ¿JXUH
Figure 6-4 Manual torque boost
2XWSXW
frequency
2XWSXW
voltage
Vb
fbf1
V1
f1: Cutoff frequency of 
manual torque boost
fb: Rated running 
frequency
Vb: Maximum 
output voltage
V1: Voltage of 
manual torque boost
Function Code Parameter Name Setting Range Default
F3-03 Multi-point V/F frequency 1 (F1) 0.00 Hz to F3-05 0.00 Hz
F3-04 Multi-point V/F voltage 1 (V1) 0.0%–100.0% 0.0%
F3-05 Multi-point V/F frequency 2 (F2) F3-03 to F3-07 0.00 Hz
F3-06 Multi-point V/F voltage 2 (V2) 0.0%–100.0% 0.0%
F3-07 Multi-point V/F frequency 3 (F3)
F3-05 to rated motor 
frequency (F1-04)
Note: The rated frequency of 
motor 2 is set in A2-04.
0.00 Hz
F3-08 Multi-point V/F voltage 3 (V3) 0.0%–100.0% 0.0%
7KHVHVL[SDUDPHWHUVDUHXVHGWRGH¿QHWKHPXOWLSRLQW9)FXUYH
 