Chapter 6 Description of Function Codes
- 84 -
Function Code Parameter Name Setting Range Default Min. Unit
FA-11 5th fault prompt 0–9 0 1
FA-12 Bus voltage upon latest fault 0–999.9 V 0 V 0.1 V
FA-13 Output current upon latest fault 0–99.00 A 0.00 A 0.01 A
FA-14 Running frequency upon latest fault 0–99.00 Hz 0.00 Hz 0.01 Hz
FA-15 Output torque upon latest fault
0.0–180.0%
(percentage of
output torque to
rated torque)
0.0% 0.1%
FA-16 Input terminal status upon latest fault 0–1023 0 1
FA-17 Output terminal status upon latest fault 0–15 0 1
These parameters record the latest ve faults and detailed information about the latest fault.
For details, see Chapter 4.
Note that Er26 is only a message prompting that the parameter setting is incorrect, and is not
stored in the fault record.
Function Code Parameter Name Setting Range Default Min. Unit
FA-18 Terminal state display * * *
It is used to view the states of the corresponding input and output terminals. When the terminal
is input active or output active, the corresponding LED segment is ON. The LEDs are arranged
as 1, 2, 3, and 4 from left to right.
A
B
C
D
E
F
G
DP
A
B
C
D
E
F
G
DP
A
B
C
D
E
F
G
DP
A
B
C
D
E
F
G
DP
1
2 3
4
The meaning of each segment is dened in the following table.
Segment
(LED1)
Meaning of ON LED2 LED3
Segment
(LED4)
Meaning of ON
A DI1 input active
Door open
running
procedure (for
viewing and
commissioning)
Door close
running
procedure (for
viewing and
commissioning)
A TA1 and TC1 ON
B DI2 input active B TA2 and TC2 ON
C DI3 input active C TA3 and TC3 ON
D DI4 input active D
Reserved
E DI5 input active E
F DI6 input active F
G DI7 input active G
DP DI8 input active DP
Blink, indicating normal
RS485 communication