EasyManua.ls Logo

INTARCON MCV-N - Cooling Capacity Data (R-404 A); MCR and BCR Series Cooling Capacity (R-404 A)

INTARCON MCV-N
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
§ MCR Series
Capacity (W)
Cold room temperature
-5 ºC 0 ºC +5 ºC +10 ºC
MCR Series
Cooling
capacity
(W)
Absorbed
power (W)
Cooling
capacity
(W)
Absorbed
power (W)
C
ooling
capacity
(W)
Absorbed
power (W)
Cooling
capacity
(W)
Absorbed
power (W)
Ambient Temp.: 35 ºC
0008
508 455 612 470 720 521 851 547
0010
621 537 738 580 901 629 1055 681
0012
701 598 838 650 1012 712 1163 766
1010
630 617 801 652 966 682 1157 727
1012
767 637 930 672 1118 717 1317 772
1014
916 761 1087 811 1275 867 1479 929
1016
1005 811 1194 880 1402 953 1628 1031
1018
1161 957 1378 1038 1579 1118 1828 1211
1024
1217 1070 1478 1201 1782 1335 2062 1462
2024
1625 1201 2020 1319 2402 1409 2888 1527
2026
1849 1324 2223 1425 2646 1531 3077 1648
2034
2080 1768 2527 1903 2987 2059 3380 2190
§ BCR Series
Capacity (W)
Cold room temperature
-25 ºC -20 ºC -15 ºC
BCR Series
Cooling
capacity (W)
Absorbed power
(W)
Cooling capacity
(W)
Absorbed power
(W)
Cooling capacity
(W)
Absorbed power
(W)
Ambient Temp:
35 ºC
0018
405 570 515 630 618 700
1018
407 618 502 671 664 752
1026
565 813 734 928 908 1039
1034
699 1015 876 1160 1051 1287
2034
840 1157 1102 1297 1366 1433
2054
1116 1617 1443 1830 1733 2005
2074
1425 1932 1689 2147 2088 2416

Related product manuals