Code Description Range Default List
MT BT
IdF
Interval between defrosting cycles. 1 ÷ 120 h 3 h Pr1
Md
F
Maximum defrosting legth.
0 ÷ 255 min 15 min Pr1
dFd
Display during defrost:
rt=real temperature ; it=last recorded temperature ; Set=set point
; dEF= dEF message ; dEG= dEGmessage.
rt, it,Set, dEF,
dEG
it Pr2
dAd
Delay after defrosting to display cold room temperature 0 ÷ 255 min 15 min Pr2
dSd
Defrosting start delay. 0 ÷ 99 min 0 min Pr2
Fdt
Time defrosting end to compressor starting-up (draining time). 0 ÷ 60 min 2 min 3 min Pr2
dP
O
Displayed if defrosting after starting-up.
n - y n Pr2
dAF
Defrost delay after fast freezing.
0 ÷ 23 h 50
min
2,0 h Pr2
FANS
FnC Fans operating mode: With compressor (C) / always on (O) /
during defrosting (y=yes / n=no).
C-n, C-y, O-n,
O-y
C-n Pr2
Fnd
Fans operation delay after defrosting. 0 ÷ 255 min 3 min 4 min Pr2
FSt
Fans stop temperature.
-50,0 ÷ 110,0
ºC
10 ºC 0 ºC Pr2
ALARMS
ALC
Temperature alarm configuration (ALU and ALL):
rE=relative ; Ab=absolute.
rE - Ab rE Pr2
ALU
Maximum temperature alarm
rE: -50,0 ÷ 110,0
ºC
Ab: 0,0 ÷ 50,0 ºC
5,0 ºC Pr1
ALL
Minimum temperature alarm
rE: -50,0 ÷ 110,0
ºC
Ab: 0,0 ÷ 50,0 ºC
5,0 ºC Pr1
AFH
Temperature alarm and fan differential 0,1 ÷ 25,5 ºC 2,0 ºC Pr2
ALd
Temperature alarm delay. 0 ÷ 255 min 0 min Pr2
dAO
Delay of temperature alarm after starting up.
0 ÷ 23 h 50
min
3 h 4 h Pr2
EdA
Alarm delay at the end of the defrosting 0 ÷ 255 min 30 min Pr2
dot
Delay of temperature alarm after closing the door 0 ÷ 255 min 30 min Pr2
doA
Delay of opened door alarm 0 ÷ 255 min 15 min Pr2
rrd
outputs restart after doA alarm n - y y Pr2
AL2
Condenser low temperature alarm -50,0 ÷ Au2 ºC
-40 ºC Pr2
Au2
Condenser high temperature alarm
AL2 ÷ 110,0
ºC
52 ºC Pr2
ALH
Differential of condenser low temperature alarm (AL2). 0,1 ÷ 25,5 ºC 5 ºC Pr2
AtH
Differential of condenser high temperature alarm (Au2). 0,1 ÷ 25,5 ºC 3 ºC Pr2
Ad2
Condenser temperature alarm delay 0 ÷ 255 min 0 Pr2
dA2
Condenser temperature alarm eclusion at starting up 0 ÷ 23h 50 min
0 Pr2
tbA
Alarm signal silencing by pressing a key. n - y y Pr2