works inttermitently and
subsequently the
pressure switch turns off
the unit.
a) Condensation control is not working
properly (only for split units)
reliable thermometer, check probe isolation,
replace probe and isolate it properly. Check
HP and LP values performance during starting
up, stop fan and modify ALH and AL2
parameters if neccesary
work.
Blocked evaporator
(frost)
a) LED ON and power in board connectors
faulty electrical supply connection or faulty
motorfan
B) LED off à wrong Pb2 probe value à
faulty probe or wrong probe wiring
Check electrical conexión or c
motorfan.
b) Check probe wiring or replace probe
b) Low oil level
c) Faulty compressor
a) Check silentbloc screws
b) Add oil to the recommended level
c) Replace
a) Unit is installed without noise insulation
a) Install insulating layer or supports under the
a) Faulty heater or solenoid valve
b) Electrical fault.
c) Faulty evaporator probe
d) Wrong defrost parameters
e) Faulty solenoid valve (only for hot gas
defrosting units)
b) check contactor and fuse
c) Check value Pb2, check connections,
replace
d) Check and adjust defrost parameters
e) Repair
Probe value is lower than cold room
temperature. The value decresases quickly
when the unit is operating
b) Room temperature probe faulty or wiring
faulty
a) wrong wiring between co
temperatura probe and evaporator probe
b) check probe wiring (electrical connection
between units for Split systems). Replace
probe
Evaporator probe faulty or wiring faulty
a) Check probe wiring (electrical interconexion
for split units). Replace probe
Check probe wiring. Replace probe
Check wiring and door switch or
parameter value and/or replace board
and the keyboard shows
the temperature value
and "---" alternatively