45
Monitoring via Ethernet/Wi-Fi (Wi-Fi only for AMT 8000 PRO alarm center)
The alarm center can report events via IP communication to monitoring companies (Intelbras IP Receiver Software), for which
the following commands must be programmed:
If you are using Wi-Fi connection before setting the monitoring options, program the following commands:
Obs.: the alarm center is connected only with 2.4 GHz routers.
» Enter in programming mode with the installer password
Enter + Installer password (factory default: 9090)
» Insert name of the Wi-Fi network to be connected
Enter + 850 + Enter + Insert name of the network + Enter
» Insert password of the Wi-Fi network to be connected
Enter + 851 + Enter + Insert password of the network + Enter
» Enable Wi-Fi / dene type of conguration of the network to be connected
Enter + 852 + Enter + TP + Enter
» TP = type of conguration
Selection Type of conguration
0 Wi-Fi disabled
1 Wi-Fi enabled / in case of AC failure, operates on battery
2 Wi-Fi enabled / only with active AC network
Obs.: » After entering each command and conrming with the
Enter
key, two quick beeps should be heard, indicating that
the programming was accepted, otherwise, there was an error.
» The network name and password must be entered exactly as it was dened in the router, considering uppercase and
lowercase letters. To change between uppercase and lowercase, press the
Deactivate
key.
» Program monitoring account
Enter + 15 + PP + Enter
, where PP = partition from 01 to 16
After the command, type the monitoring account number with 4 digits and press the
Enter
key to conrm.
» Program the reporting mode.
Enter + 17 + 4 + 0 + 0 + Enter
» Program communication priority (Ethernet only)
Enter + 19 + 0 + Enter
» Program destination IP
Enter + 801 + I + Enter
, where I = 1 or 2 (destination IP 1 or destination IP 2)
After the command, type the IP number of the monitoring company (example: 192.168.001.100) and press the
Enter
key to conrm.
» Program IP network communication port
Port 1 =
Enter + 802 + 1 + Port number with 4 digits + Enter
Port 2 =
Enter + 802 + 2 + Port number with 4 digits + Enter
» Program destination domain name (DNS)
If you do not want to use DNS move to the next command, otherwise, type.
Enter + 803 + D + Enter
, where D = 1 or 2 (DNS 1 or DNS 2)
After the command, type the DNS domain name and press the
Enter
to conrm.
» Program monitoring options via IP
Enter + 830 + Enter
After the command, using the keyboard keys, enable the desired option from 1 to 4, where:
» 1: enables the sending of events to the monitoring company 1.
» 2: enables the sending of events to the monitoring company 2.
» 3: enables the domain name (DNS) of the monitoring company 1.
» 4: enables the domain name (DNS) of monitoring company 2 and press the
Enter
key to conrm.