II/IO - SCV1
35
CLEANING COILS - The coil should be washed out with water, or
blown out with compressed air. Clean the coil annually, or as
required by the location or outdoor air conditions. Inspect the coil
monthly and clean as required. Dirt and debris may pass through
the first coil section, then become trapped between the rows of
fins and restrict the condenser air flow. Use a flashlight to
determine if any dirt or debris has collected between the coil
sections. Clean coil as follows:
1. Turn off unit power.
2. Using a water hose, or any other suitable equipment, flush
the coil from the outside to remove dirt. Be sure to flush all
dirt and debris from the drain holes in the base of the unit.
THE INTERNAL CURRENT AND TEMPERATURE SENSITIVE
OVERLOAD OF COMPRESSORS resets automatically when the
internal compressor temperature drops to a safe level (overloads
may require up to 30 minutes to reset). When an internal overload
is suspected of being open, check by using an ohm-meter for
continuity test. If necessary, refer to your local distributor for
complete information.
TABLE 2: ELECTRIC WIRE SIZE
TOP VIEW
COMPRESSOR
CONDENSER COIL
FAN MOTOR
FAN
LIQUID VALVE
SUCTION VALVE
INDOOR FUSE CIRCUIT ELECTRIC
MODEL CONTROL BREAKER WIRE SIZE (mmÇ)
II-09 3.15A / 250V 15A / 2P. 1.0
II-12 3.15A / 250V 15A / 2P. 1.5
II-18 3.15A / 250V 20A / 2P. 2.5
II-22 3.15A / 250V 25A / 2P. 4.0