2 / 48    P/N MAINST-ATS111x (ML) • REV D • ISS 24JUN14 
EN: Installation Sheet 
Mounting the unit 
The RAS cover is hinged at the bottom. To open, grasp the 
cover at the sides or the top and pull gently — the cover will 
swing down on its pins. The cover may be fully removed by 
gently prising one of the pins away from the body of the RAS 
and pulling. A locking screw holds the metal mounting plate at 
the rear. To remove the metal mounting plate, loosen the 
screw by at least 8 mm (0.315 in.), sliding the mounting plate 
down, and then pulling the bottom of the mounting plate away 
from the body of the RAS. 
Attach the metal mounting plate to mounting surface using the 
three screws provided. If rear cable entry is used (through the 
mounting plate), cut a hole in the mounting surface for cable 
access. Set the RAS address using DIP switches 1 through 4 
(see “RAS DIP switch settings” below). Set the bus termination 
switch (DIP switch 5), if required. Terminate the bus cabling. 
WARNING: All power should be turned off to the control panel 
before wiring the RAS. 
Insert plastic cable entry blanking plugs (provided) into the rear 
of the RAS to blank any unused cable entry channels. Place 
the RAS onto the mounting plate and lock in place by moving 
the unit down by about 8 mm (0.315 in.) Tighten the locking 
screw at the base of the RAS till firm. Do not over-tighten. 
Figure 2 
1.  Cable entry 
2.  DIP switches 
3.  LAN terminals 
4.  Tamper switch 
5.  Locking screw 
Connecting control panel to keypad 
Refer to the ATS control panel installation guide for 
instructions. 
Tamper switch 
See figure 2. 
The rear tamper switch must be sealed for the system to work 
correctly. The tamper switch is sealed by mounting the RAS 
onto the mounting plate, and then moving it to the locked 
position. In operation, the LCD display will show “RAS Tamper” 
when not sealed. 
RAS DIP switch settings 
See figure 3. 
A row of DIP switches is located on the rear of the RAS 
(figure 2) and is used for setting the RAS address and the bus 
termination (TERM) condition. These settings are described in 
the following sections. 
•  TERM switch: Use switch 5 to set TERM to On, if needed. 
There must be no more than two TERM switches or links 
set to On for any bus. Refer to the control panel 
installation guide for details about the use of TERM 
switches or links. 
•  RAS address: Set the RAS address using switches 1 to 4. 
Connections 
See figure 4. 
•  +13.8 VDC: The RAS can be powered using the bus “+” 
and “−” power from the control panel, if the distance 
between the RAS and the control panel does not exceed 
100 m (328 ft.) Otherwise the RAS can be powered by 
AUX PWR from a DGP, or by an auxiliary power supply. 
•  D+/D−: D+ is the data positive connection and D− is the 
data negative connection of the data bus. 
The RAS is connected to the ATS panel via the RS485 data 
bus, up to 1.5 km from the control panel or the four-door 
controller DGP. It is recommended to use two-pair twisted, 
shielded data cable (WCAT 52/54). The shield of any bus 
cable must be connected to system ground at one end only. 
The ATS111x RAS is not provided with an Earth connection for 
this purpose. If the bus is daisy-chained to the RAS, ensure 
that the shield of the cable is jointed to provide continuity of 
data cable shield. 
•  RTE: An RTE button (normally open, momentary push-
button switch) can be connected across the “IN” and “0 V” 
terminals (see figure 4). When pressed, the button 
controls the request to exit function to the panel. 
•  IN: A request to exit button (normally open, momentary 
push-button switch) can be connected across “IN” and “−”. 
When pressed, this button controls the request to exit 
function. 
•  OUT: Open collector output. Use the first output number of 
the output controller assigned to the RAS. Refer to the 
ATS control panel programming manual for details. 
Note: When using IN or OUT pins, it is recommended to use a 
shielded cable (WS104). Ensure that the shield of the cable is 
connected to ground at one end only. 
Status LED indications 
See figure 1. 
Green: The Power LED is on when the control panel 
is powered by the AC supply. 
Yellow: The Fault LED illuminates to indicate 
detection of a system fault. 
Blue: The Access LED flashes when access to an 
area assigned to the RAS is granted. 
Red: The Alarm LED illuminates when there is a 
system tamper or an area assigned to the RAS is in 
alarm state. The area may be identified by viewing 
the 16 area LEDs visible when the RAS cover is 
open or removed. 
Area LED indications 
See figure 1. 
When the RAS cover is open or removed, 16 red LEDs are 
visible at the bottom of the RAS. Each LED represents an 
area, and the indications are as follows: 
•  The LED illuminates when its corresponding area is 
armed. 
•  The LED flashes slowly when a fault is detected or when 
an alarm occurs, in disarmed state.