Chapter 5: Menu reference 
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual  245 
8.4.5 Forced set options 
 
4 Forced set opt 
     >Inh unset< 
The Forced set options menu defines when the forced set is possible. The 
following options are available. 
•  Inhibit till unset : Zone is inhibited until the area is unset.   
•  Inhibit exit : Zone is inhibited until the exit time expires.  
•  Inhibit close : Zone is inhibited until its state changes to normal.  
8.4.6 Pending alarms 
 
5 Pending alarms 
        >Enable< 
If set to Enable, the Pending alarms option requires all alarms and faults to be 
acknowledged. 
Enable EN Gr3 is equal to Enable except that faults and tampers can only be 
acknowledged by level 3 user (installer).  
When disabled, it does not require alarm acknowledgement. During unsetting or 
resetting the area, the alarm is acknowledged automatically. However, each 
alarm and fault is shown 3 times on the keypad screen. 
8.4.7 AS fault retry 
 
6 AS fault retry 
    >15 minutes< 
The Autoset retry on system faults option defines if and when the system repeats 
an attempt to set automatically in if a system fault has made an autoset 
impossible. The following options are available: 
•  Off 
•  15 minutes 
•  30 minutes 
•  1 hour 
•  2 hours 
•  3 hours 
•  4 hours 
See “Autoset” on page 91 for more details. 
8.4.8 AS user retry 
 
8 AS user retry 
    >15 minutes< 
The Autoset user retry option defines a time for which a normal user can 
postpone an autoset. The following options are available: 
•  Disabled (autoset postponing is not allowed)