Chapter 5: Menu reference 
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual  247 
8.5.1.3 Multiple badge 
 
This setting is only applicable where the door has been programmed so that 
presentation of a card three times will arm/disarm the system and the user is 
authorised to arm /disarm. 
The Multiple badge time is the amount of time allowed between the first 
presentation of the card and the third presentation of the card. If the card is not 
presented three times before the time expires, the user will need to commence 
the function again.  
8.5.1.4 Re-lock delay 
 
This setting only applies where the door has been programmed so the unlock 
relay will not re-lock until after the door is closed.  
This feature is provided for Drop Bolts and Maglocks etc. where the door must be 
closed before the unlock relay locks the door. 
The Re-lock delay time is the amount of time between the door being closed and 
the unlock relay deactivating (re-lock). This allows a settling time to ensure that 
the lock mechanisms are aligned. 
8.5.2 DGP options 
 
The menu contains door controller settings. 
8.5.2.1 Map relays 
 
Defines whether door controller unlock outputs can be controlled as standard 
outputs. 
•  Yes: Door unlock outputs can be controlled by the control panel as its 
outputs.  
•  No: Door unlock outputs can only be activated by door controller when using 
door unlock user menu, or upon presenting a valid card.