Zone state
EOL
Connection
details [1]
Measure [2]
Short
Masking
Normal
Alarm
Fault
Open
3K74
(Item 4)
R (kΩ)
<1.25
1.25
2.45
2.45
4.99
4.99
9.98
>9.98
RA=3.74 kΩ, RT=1.87 kΩ,
RF=1.87
U (V)
<2.90
2.90
4.80
4.80
7.10
7.10
9.40
>9.40
3K3
(Item 4)
R (kΩ)
<1.10
1.10
2.20
2.20
4.40
4.40
8.80
>8.80
RA=3.3 kΩ, RT=1.65 kΩ,
RF=1.65
U (V)
<2.60
2.60
4.40
4.40
6.70
6.70
9.00
>9.00
2K
(Item 4)
R (kΩ)
<0.67
0.67
1.33
1.33
2.67
2.67
5.33
>5.33
RA=2 kΩ, RT=1 kΩ,
RF=1
U (V)
<1.70
1.70
3.00
3.00
5.00
5.00
7.30
>7.30
1K5
(Item 4)
R (kΩ)
<0.50
0.50
1.00
1.00
2.00
2.00
4.00
>4.00
RA=1.5 kΩ, RT=0.75 kΩ,
RF=0.75
U (V)
<1.30
1.30
2.40
2.40
4.10
4.10
6.30
>6.30
2K2+4K7
(Item 3)
R (kΩ)
<3.60
3.60
5.60
5.60
8.20
>8.20
RA=2.2 kΩ, RT=4.7
U (V)
<6.00
6.00
7.50
7.50
8.80
>8.80
1K
(Item 7)
R (kΩ)
<0.51
4.52
40.00
0.51
1.52
1.52
2.94
2.94
4.52
>40.00
RA=1 kΩ, RT=1 kΩ,
RF=12
U (V)
<1.35
6.24
12.33
1.35
3.36
3.36
5.29
5.29
6.74
>12.33
8K2
(Item 5)
R (kΩ)
<1.50
1.50
5.84
5.84
14.25
>14.25
RA=8.2 kΩ, RT=8.2
U (V)
<3.33
3.33
7.52
7.52
10.33
>10.33
8K2
(Item 6)
R (kΩ)
<1.50
14.25–
45.00
1.50
5.84
5.84
10.07
10.07–
14.25
>45.00
RA=8.2 kΩ, RT=8.2 kΩ,
RF=8.2
U (V)
<3.33
10.33–
12.48
3.33
7.52
7.52
9.37
9.37
10.33
>12.48
[1] Refer to Figure 19 on page 27.
[2] Zone resistance R (kΩ), zone voltage U (V).