Chapter 3: System functions 
82  Advisor Advanced ATSx500A(-IP) Installation and Programming Manual 
The test is cancelled if the Clear key is pressed. There is also a maximum time 
limit on the test, set in “8.1.3.3 Walk test time” (see page 234). The test fails if 
this timer expires. If engineer reset fails and inhibit reporting has not been 
enabled when accessing the programming mode then a message is sent to the 
central station to indicate that the test failed (see “Accessing the installer 
programming menu” on page 108). 
Single zone walk test 
You can also use “1.2.5.3 Single zone WT” on page 129 to perform a single zone 
walk test on the same rules as the engineer walk test described above. 
Walk test mode 
A special walk test mode allows verification of the whole alarm system 
functionality. In this mode, a service engineer or a guard must perform as many 
actions on the operating alarm system as possible. This may include set and 
unset, entry and exit, activating all detectors and tampers. The system operates 
as usual, sending all alarm and tamper events to the central station, except none 
of system sirens is active. 
This allows the central station operator to review all received alarms and verify if 
appropriate system functions are working properly. 
Active walk test 
Active walk test allows you to test alarm reporting in case of a confirmed alarm 
simulation (required by ACPO). 
Choose zone A for A-alarm, and zone B for B-alarm. 
First, activate zone A, and then zone B. 
The panel will simulate a confirmed alarm and send all appropriate reporting 
events to the central station. 
Notes 
•  The tested zones must be one of the following types: 1. Alarm, 4. Fire, 5. 
Panic, 6. 24H, 7. Tamper, 13. Fire door. 
•  Options “4.1.n.6.11 Engineer walk test” on page 175 for these zones must be 
enabled. 
•  The user privileges in this area must have Walk test allowed. See “3.2 User 
groups” on page 168 for more details. 
User walk test 
If the user walk test is configured and enabled, the user is requested to perform 
the user walk test prior to setting an area. The frequency of this request is 
defined in “1.2.5.2.7 Frequency” on page 128. If the option “1.2.5.2.8 Need to 
set” on page 128 is enabled, setting an area without prior user walk test is not 
allowed.