120/240 VAC Three wire with grounded
neutral.
Found at Service entrances
and Meter Cans.
Line
Line
Grounded/
Neutral
120 v
120 v
240 v
WHITE
BLACK
BLACK
120/240 VAC Three wire with separate ground.
Found in Main Disconnect Switches,
Main Distribution panels, Load Centers
Sub panels and equipment locations.
Line
Line
Neutral
Ground
120 v
120 v
240 v
120 v
BLACK
WHITE
120 VAC Two wire single phase with
separate ground.
Found at connections for individual
pieces of equipment such as pumps
and single phase motors. NOTE: Both
Black wires connect to Line.
Line
Neutral
Ground
0 v
120 v
120 v
WHITE
BLACK
BLACK
Model AG24013 and AG2401C3
Type 1 or Type 2 Surge Protection Device
INSTALLATION INSTRUCTIONS
BLACK
Risk of Electric Shock
WARNING
• Thoroughlyreadinstructionsbeforeinstallingunit.
• InstallationandServicetobeperformedbya
qualiedlicensedelectrician.
• Intendedforindoororoutdooruse.
Type 1 installation:
Atypicalinstallationofatype1SPDwillbeconnectedbetweenthesecondaryoftheservicetransformerandthe
linesideoftheservicepanel.ThisinstallationisintendedtobeinstalledwithoutovercurrentprotectiontotheSPD.
Type 2 installation:
Atypicalinstallationofatype2SPDwillbeconnectedtotheloadsideoftheservicepanelandisintendedtobe
installedwithovercurrentprotectiontotheSPD.
1. Determininglocation:
• Ensureconductorlengthsareasshortandstraightaspossibleforbestperformance.Donotcoilexcess
wire.TheSPDfunctionsbestifallbendsinwiresarerounded,ideallytoa4”radius.Hard90degreebend
willreduceefciency.Cutallleadstothecorrectlength.Donotcoilexcessleads.
• Installappropriateweatherproofttingsiftheunitistobemountedoutside.
• BracketpartnumberAG1BRKTisalsoavailableifneeded.
2. Connectwiresasshownwithindiagrams.Ifyourapplicationdoesnotmatchoneofthediagramsbelow
consultyoursupplier.
3. Ensureallmountingandelectricalconnectionsarecorrectandsecurelyfastened.Onceenergizedthegreen
indicatorLEDwillbeON.
Maintenance:
¡ACVoltageSPD:
• PeriodicallycheckSPDtoensuregreenindicatorLEDisON.IfgreenLEDisOFFprotectionhasdiminished
andtheSPDshouldbereplacedimmediately.
120/240 VAC SINGLE PHASE
• Allwiringmustcomplywithallstateandlocal
electricalcodesincludingtheNationalElectrical
Codeand/orCanadianElectricalCode.
• Suitableforuseonacircuitcapableofdelivering
notmorethan50,000rmssymmetricalamperes.
• Thisunitcontainsnoserviceableparts.
• Thisproductdoesnotprotectagainstdirect
lightningstrikes.
IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
http://waterheatertimer.org/Intermatic-Compressor-Defender.html

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Intermatic AG2401C3 and is the answer not in the manual?

Intermatic AG2401C3 Specifications

General IconGeneral
TypeSurge Protective Device
Voltage Rating240 VAC
Maximum Surge Current40kA
Response TimeLess than 1 nanosecond
PhaseSingle Phase
Poles2
Enclosure TypePlastic
TerminalsScrew Terminals
MountingDIN Rail
NEMA RatingNEMA 4
Trip SensitivityNot applicable
Operating Temperature-40 to 60°C
Warranty5 Year Limited