Model IG1240RC3
Type 1 or Type 2 Surge Protection Device
INSTALLATION INSTRUCTIONS
Risk of Electric Shock
WARNING
• Thoroughlyreadinstructionsbeforeinstallingunit.
• InstallationandServicetobeperformedbya
qualiedlicensedelectrician.
• Intendedforindoororoutdooruse.
Type 1 installation:
Atypicalinstallationofatype1SPDwillbeconnectedbetweenthesecondaryoftheservicetransformerandthe
linesideoftheservicepanel.ThisinstallationisintendedtobeinstalledwithoutovercurrentprotectiontotheSPD.
1. Determinelocation:
• Ensureconductorlengthsareasshortandstraightaspossibleforbestperformance.Donotcoilexcess
wire.TheSPDfunctionsbestifallbendsinwiresarerounded,ideallytoa4”radius.Hard90degreebend
willreduceefciency.Cutallleadstothecorrectlength.Donotcoilexcessleads.
• Installappropriateweatherproofttingsiftheunitistobemountedoutside.
2. Connectwiresasshowningure1.
3. Ensureallmountingandconnectionsarecorrectandsecure.OnceenergizedthegreenindicatorLEDwillbeON
andvisiblethroughthecoveroftheSPD.
Type 2 installation:
Atypicalinstallationofatype2SPDwillbeconnectedtotheloadsideoftheservicepanelandisintendedtobe
installedwithovercurrentprotectiontotheSPD.
1. Determininglocation:
• Ensureconductorlengthsareasshortandstraightaspossibleforbestperformance.Donotcoilexcess
wire.TheSPDfunctionsbestifallbendsinwiresarerounded,ideallytoa4”radius.Hard90degreebend
willreduceefciency.Cutallleadstothecorrectlength.Donotcoilexcessleads.
• Installappropriateweatherproofttingsiftheunitistobemountedoutside.
• IG1240FMP33isalsoavailableforushmountapplications.
2. ConnectthegreenwirefromtheSPDtothegroundbusinthepanel.
• Connectionmayalsobemadetotheneutral/groundbusbarifpaneldoesnothaveaseparategroundbusbar.
3. ConnectthewhitewirefromtheSPDtotheneutralbusbarinthepanelasshowningure2.
4. Connectthetwoblackwirestoacircuitbreakerasshowningure2.ForbestperformancefromSPDthe
maximumrecommendedcircuitbreakersizeof240V,20A,2-poleshouldbeused.
5. Ensureallmountingandelectricalconnectionsarecorrectandsecurelyfastened.Onceenergizedthegreen
indicatorLEDwillbeONandvisiblethroughthecoveroftheSPD.
Maintenance:
¡ACVoltageSPD:
• PeriodicallycheckSPDtoensuregreenindicatorLEDisON.IfgreenLEDisOFFprotectionhasdiminished
andtheSPDshouldbereplacedimmediately.
• Allwiringmustcomplywithallstateandlocal
electricalcodesincludingtheNationalElectrical
Codeand/orCanadianElectricalCode.
• Suitableforuseonacircuitcapableofdelivering
notmorethan50,000rmssymmetricalamperes.
• Thisunitcontainsnoserviceableparts.
• Thisproductdoesnotprotectagainstdirect
lightningstrikes.
IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Line
Line
Neutral
Ground
GREEN
WHITE
BLACK
BLACK
120 v
120 v
120 v
240 v
120 v
MainBreaker
2-Pole,20Acircuit
breakershown
A=Black(Line)
B=Black(Line)
C=Neutral(White)
D=Green(Ground)
Figure1
Type1Installation
Figure2
Type2Installation
http://waterheatertimer.org/How-to-wire-Whole-house-surge-protector.html
Question and Answer IconNeed help?

Do you have a question about the Intermatic IG1240RC3 and is the answer not in the manual?

Intermatic IG1240RC3 Specifications

General IconGeneral
TypeSurge Protective Device
Voltage Rating120/240 VAC
Maximum Surge Current40kA
Response TimeLess than 1 nanosecond
MountingPanel Mount
Surge Protection TypeType 2
PhaseSingle Phase
Poles2
TerminalsScrew Terminals

Summary

Safety Instructions and Installation Types

Important Safety Instructions

Mandatory safety warnings and compliance requirements for electrical installations.

Type 1 SPD Installation

Detailed steps for installing a Type 1 Surge Protection Device without overcurrent protection.

Type 2 SPD Installation

Detailed steps for installing a Type 2 Surge Protection Device with overcurrent protection.

Maintenance and Indicator Check

Guidance on periodic checks of the surge protector's indicator LED.

Product and Connected Equipment Warranty

Warranty Coverage Details

Explains coverage for product defects and damage to connected equipment within five years.

Warranty Exclusions

Lists conditions and damages not covered by the limited warranty, including misuse and specific events.

Warranty Claim Procedure

Step-by-step instructions for submitting a warranty claim, including required documentation.

Related product manuals