Do you have a question about the Intermatic IG3240RC and is the answer not in the manual?
Type | Surge Protective Device |
---|---|
Voltage Rating | 120/240 VAC |
Maximum Surge Current | 40kA |
Response Time | Less than 1 nanosecond |
Mounting | DIN Rail |
Poles | 2 |
Warranty | 5 years |
Terminals | Screw |
Standards | UL 1449 |
Electricity is dangerous; follow safety rules. Never work on equipment with the electricity turned "ON".
Electrical ground is required for this unit to function properly and safely.
Select a mounting location for the Surge Protection Device (SPD) and verify 240 volts between breakers.
Verify all parts are present, including the panel protector, threaded connector, locking nut, and conduit nut.
Select the mounting location for the protector at the panel and contact support if the panel differs from the diagram.
Do not attempt work without a main power shut-off. Verify circuits are off using a tester before proceeding.
Carefully remove the front trim panel and select a knockout for protector wiring entry, aiming for shortest wire length.
Insert protector wire and connector into the knockout, securing with the locknut. Use flush mounting kit if needed.
Connect green wire first, then white, then black wires to breakers. Ensure wires are rounded and cut to length.
Route and connect the green wire to the ground bus bar or neutral bus bar for safety purposes.
Route and connect the white wire to the neutral bus bar provided in the breaker panel.
Connect the two black wires to separate 15 or 20 amp breakers, not to each other, for full 240 volt protection.
Check wire security, confirm voltage, and replace the front trim panel. Turn off main breaker before moving wires.