EasyManua.ls Logo

Intertherm M1B Series - Troubleshooting (Continued); Oil Gun Control Status and Lockouts; Burner Lockout and Cad Cell Issues

Intertherm M1B Series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28


Burner does not start with a call for heat
• Checktheelectricalsupplytofurnace.
• VerifythefurnacedoorswitchisintheON position.
• Check for line voltage (115 VAC) at the oil primary
control.
• CheckindicatorLEDwithburneroff,nocallforheat(no
ame).SeeTable 9, (page 29).
- If green LED indicator is on, the cad cell is seeing
stray light or the cad cell of controller is defective.
- If green LED indicator is off, go immediately to step
5.
- IfLEDindicatorisashing(redorgreenonBeckett
7505 control), refer to the next step 1 below - Reset
primary control.
• JumperT to T terminals on primary control.
- If burner starts, check thermostat or limit wiring
connections.
- If burner does not start, turn off power. Check all
wiring connections.
- If burner does not start, replace primary control.
Burner starts & then locks out on safety with
Honeywell R7184 LED indicator flashing ½
second on, ½ second off. For Beckett 7505
control, the red LED will flash
1. Reset primary control: To reset the control from (soft)
lockout, the button needs only to be pressed and
released. If the R7184 control is in restricted mode,
press and hold the button for 45 seconds - until the LED
ashesonce.Ifthe7505controlisinrestrictedmode,
press and hold the button in for 15 seconds until the
red turns off and the yellow LED turns on.
 Restricted Lockout: If the control locks out three
times in a row without a complete heat cycle between
attempts, the lockout becomes a restricted (hard) lockout.
2.If the LED indicator stops ashing and the ignition
remains off, the primary control could be defective. If
line voltage is present at the igniter terminals, and there
is no ignition, the igniter is likely defective and needs
to be replaced.
3.Ifthestopsashing,burnerturnson,butthecontrol
locks out again, check the cad cell. If the cad cell is
operational, replace the primary control.
4.If the LED continues to ash at the interval listed
above, verify that the control is not in restricted mode.
If in restricted mode, reset it. If not in restricted mode,
replace the control.
5. If the (LED indicator for R7184 control; green LED for
7505control)staysoffwhiletheameison,checkthe
cadcellsightingforviewoftheame.
6. If the burner locks out, check the cad cell resistance.
See Table 8.
7. If the burner stays running, the system is operational.
8. If the (LED indicator for R7184 control; green LED for
7505 control) is off, check the cad cell assembly after
disconnecting the line voltage.
Burner will not start and the LED indicator
is flashing at 2 seconds on, 2 seconds off
for R7184 (or green LED is flashing for 7505)
• Holdtheresetbuttondownfor1-2seconds.IfLED
indicatorcontinuestoash,waitfor60-70seconds.If
itstillcontinuestoash,replacetheprimarycontrol.
• Honeywell R7184 control: To check cad cell resistance,
press and release the button during the run mode, with
theigniteroff.TheLEDwillashtoindicatethecadcell
resistance. For proper burner operation, it is important
that the cad cell resistance is under 1600 Ohms. For
cad cell resistance, see Table 8.
• Beckett 7505 control: To check cad cell resistance,
unplug the cad cell leads (yellow wires) from the control.
Measure the resistance with a meter in the conventional
way (when a ame is present). For proper burner
operation, it is important that the cad cell resistance is
under 1,600 Ohms.
Table 8
Table 8. 
sensing flame
 
1 0-400
2 400-800
3 800-1600
4 >1600

Table of Contents