EasyManua.ls Logo

Intertherm M1B Series - Furnace Installation Procedures; Locating and Cutting Duct Openings; Standard Duct Connector Installation

Intertherm M1B Series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8

These Installation procedures are suggested for
typical furnace installations. Since each installation is
different, the sequence of instructions may differ from
the actual installation. Only qualified HVAC technicians
should install this furnace.
The installer must be familiar with and comply with all
codes and regulations applicable to the installation of
these heating appliances and related equipment. In
the absence of local codes, the installation must be in
accordance with the current provisions of one or more of
the following standards.
• Federal ManufacturedHome Constructions & Safety
Standard (H.U.D. Title 24, Part 3280.707[a][2])
• AmericanNationalStandard(ANSI-119.2/NFPA-501C)
for all recreational vehicle installations.
• AmericanNationalStandard(ANSI-Z223.1/NFPA-54)
and/or CAN/CSA B149 for all gas-fired furnace models.
• American National Standard (ANSI-Z95.1/NFPA-31)
and/or CSA B139 for all oil-fired furnace models.
• AmericanNationalStandard(ANSI-C1/NFPA-70)and/or
CSA 22.1 Canadian Electric Code Part 1 for all electrical
field wiring.
• UnitshavebeenresearchedunderstandardsUL307A
& B, UL727-1999, ANSI Z21.47b/CSA 2.3b-2008, and
CSA B140.10.

• Thefurnacemustbeleveledatinstallationandattached
to a properly installed duct system. 
  See page 7 for
circulating requirements.
• The furnace must be installed so that all electrical
components are protected from water.
• Thedimensionsoftheroomoralcovemustbeableto
accommodate the overall size of the furnace and the
installation clearances listed in Table 1, (page 6)
and Figure 1 (page 6)
• The furnace must be installed upstream from a
refrigeration system.
• The M1 Series gas and M5 Series oil furnace is
certiedforuseonwoodooringorsupports,butmust
be installed on top of a duct connector. This factory
suppliedaccessorymustbeinstalledintheoorcavity
and attached to the supply air duct before the furnace
is installed.

Floor cut-outs and fuel line holes must be carefully located
to avoid misalignment of the furnace, and vent piping.
To locate standard ducts see Figure 6 (page 9). For
round ducts, see Figure 7.
1. Measure 10” from the rear wall or alcove and mark the
centerlineofthecut-outontheoor.
2. Using the centerline as a starting point, draw the rest
of the duct cut-out to the dimensions shown in Figure
6 or Figure 7.
3.Cutouttheooropening1/16”largerthantheactual
cutout drawn. This will allow some clearance when
installing the duct connector.
4.Measurefromthetopoftheoordowntothetopofthe
supplyairducttoobtainthedepthoftheoorcavity.
Thedepthoftheoorcavityshownas“X”in
Figure 9 (page 9) will determine the correct duct
connector.
5. Determine which duct connector to use from Table 3
(page 9).
6. Measure and drill gas hole and cut out for cooling coil
(if applicable). See Figure 6 or Figure 7.
Standard Duct Connector Installation
The standard duct connector is designed for use on ducts
12” in width. However ducts narrower than 12” may not
allow sufficient clearances for this type of installation. For
an alternate installation method, see page 9.
1.Center the duct connector in the oor opening with
bottom tabs resting on top of the supply air duct.
2. Mark the cut-out area on the supply air duct by tracing
around the connector tabs of the duct connector. See
Figure 8 (page 9).
3. Remove the duct connector and cut out the marked
area of the supply air duct 1/4” larger the actual cutout
drawn.
4.Installtheductconnectorbackintheooropeningwith
the bottom tabs extending into the supply air duct.
5. Install the mounting plate under the back side of the
duct connector as shown in Figure 8. Align the screw
holes in both components.
6. Secure the duct connector and the mounting plate to
thewoodoorwithappropriatesizescrews.
7. Bend the connector tabs on the bottom of the duct
connector upwards and as tight as possible against
the supply air duct.
8. Bend both tabs up 90° on the mounting plate. See
Figure 10 (page 10).
9. Seal all connections with industrial grade sealing tape
or liquid sealant.
 Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specific to your area.

Table of Contents

Related product manuals