Troubleshooting
Page 80
5.8 EC (Refrigerant Leakage Detection diagnosis and solution)
Description: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
In the beginning 8 minutes after the compressor starts up, if T2<Tcool-1°C does not keep continuous 4 seconds and
compressor running frequency higher than 50Hz does not keep continuous 3 minutes, and this situation happens 3
times, the display area will show “EC” and AC will turn off.
Recommended parts to prepare:
Faulty T2 sensor
Faulty indoor PCB
System problems, such as leakage or blockages
Troubleshooting and repair:
Power off, then restart the unit 2 minutes later.
Are any leakages
present?
Check System for blockages
and
clear
blockages if present.
Does a problem remain?
Put your hands in front of the
indoor air outlet.
YES
Is there cool
air blowing out from
indoor air outlet?
Is
it
securely
attached?
Replace the
indoor PCB
YES
Check the T2 sensor.
YES
Check system for leakages.
NO
NO
Repair the leakage and
recharge the refrigerant.
YES
NO

Table of Contents

Other manuals for INVENTOR O3MVO32-09

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVENTOR O3MVO32-09 and is the answer not in the manual?

INVENTOR O3MVO32-09 Specifications

General IconGeneral
BrandINVENTOR
ModelO3MVO32-09
CategoryAir Conditioner
LanguageEnglish

Related product manuals