When the AC enter into the information enquiry status, it will display the code value in the next 25s, the
details are as follows.
T1,T2,T3,T4,
T2B,TP,TH,
Targeted
Frequency,
Actual
Frequency
1. All the displaying temperature is actual
value.
2. All the temperature is °C no matter what
kind of remote controller is used.
3. T1,T2,T3,T4,T2B display range:-25~70,
TP display range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it
will display the maximum value or minimum
value.
Indoor fan
speed
/Outdoor fan
speed
Low speed, Medium
speed, High speed,
Turbo
For some big capacity motors.
Actual fan
speed=Display value
turns to decimal
value and then
multiply 10. The unit
is RPM.
For some small capacity motors,
display value is from 14-FF(hexadecimal),
the corresponding fan speed range is from
200-2550RPM.
Actual EXV opening
value=Display value
turns to decimal
value and then
multiply 2.
Compressor
continuous
running time
If the actual value exceeds the
range, it will display the maximum
value or minimum value.
Causes of
compressor
stop.
For the detailed
meaning, please
consult with engineer