GD200A series VFD Function parameters
-40-
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can cancel
the impact on the output voltage of the VFD
because of the bus voltage fluctuation.
0: G type, for the constant torque load of rated
parameters
1: P type; for the variable torque load of rated
parameters (fans and water pumps)
GD200A series VFDs can use G/P type, the
available motor power of G type is small one
power file than that of P type.
Function
restore
parameter
0: No operation
1: Restore the default value
2: Clear fault records
3: Lock the keypad
Note:
The function code is restored to 0 after the
operation corresponding to the selected option is
performed.
Restoring to the default value will cancel the user
password. Exercise caution before using this
function.
When P00.18=3, all the other function codes
except P00.18 are read only.
P01 Group Start and stop control
0: Start directly: start from the starting frequency
P01.01
1: Start after DC braking: start the motor from the
starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in the
cases where reverse rotation may occur to the low
inertia load during starting.
2: Start after speed tracking: start the rotating
motor smoothly after tracking the rotation speed
and direction automatically. It is suitable in the