What to do if INVT HT1101L shows bypass overload timeout?
- CChristopher WoodAug 8, 2025
If the INVT UPS is on bypass and overloaded, and the overload time exceeds the bypass overload capacity, the UPS will shut down the output, causing a power loss to the loads. To resolve this, remove some loads, restart the UPS, and then turn on the loads one by one while the UPS is working normally.