HT33 Series User Manual
Safety Precautions
This manual is about the installation and operation of HT33 Series UPS (Hereinafter referred to as
UPS).
Please carefully read this manual prior to installation.
The UPS must be debugged and maintained by the engineer commissioned by the manufacturer or
the agent. Otherwise, human safety may be endangered and the damage of UPS shall not belong to the
warranty scope.
UPS is only used for commercial / industrial purpose and cannot be used as power of life support
equipment.
APPLICABLE STANDARDS
This product complies with CE 73/23 & 93/68 (low voltage safety) and 89/336 (EMC) , and EMC
standards of Australia and New Zealand (C-Tick) , and the following UPS product standards:
*IEC62040-1-1-General and safety requirements for use in operator access area
*IEC/EN62040-2 EMC requirements CLASS C3
*IEC62040-3 Performance requirements and test methods
Continued compliance requires installation in accordance with these instructions and the use of
manufacturer approved accessories only.
WARNING- High earth leakage current
Earth connection is critical before connecting the input supply (include both utility supply and
battery) . This equipment must be earthed in accordance with local electrical authority codes of
practice.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the equipment,
should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers ( RCCBs) must be selected insensitive to DC unidirectional pulses
( class A ) and transient current pulses ( RCCBs) .
Note it that the earth leakage currents of the load will also flow across RCCB or RCD.
Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools
and should be carried out only by trained personnel. The components that can only be accessed by
opening the protective cover with tools cannot be maintained by user.
This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator
access area UPS”.Dangerous voltages are present within the battery box. However, the risk of
contact with these high voltages is minimized for non-service personnel. Since the component with
dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of
touching high voltage component is minimized. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures in this manual.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the INVT HT 33015 and is the answer not in the manual?

INVT HT 33015 Specifications

General IconGeneral
BrandINVT
ModelHT 33015
CategoryUPS
LanguageEnglish

Summary

Safety Precautions

Applicable Standards

Lists compliance with CE, EMC, and UPS product standards like IEC62040.

High Earth Leakage Current Warning

Details earth leakage current exceeding 3.5mA and RCCB/RCD selection.

High Voltage Battery Warning

Chapter 2 Installation Guidance

Introduction and Warnings

Overview of installation, warnings for authorized engineers and battery hazards.

Distribution Room Requirements

UPS requires indoor installation in a clean, ventilated environment with adequate cooling.

Cable Connection Procedures

Describes connection procedures for power cables, including battery connections.

Chapter 3 Operations

Specific Operation Modes

Details Normal, Battery, Auto-Restart, Bypass, Maintenance, and ECO modes.

Battery Self-checking and Protection

Details advanced battery functions like self-checking, maintenance, and protection features.

Chapter 4 Parallel Operation System Installation

Chapter 5 Operating Procedures

Switching Operation Modes

Explains procedures to switch between Normal, Battery, and Bypass modes.

Maintenance Bypass Procedures

Details switching to and from maintenance bypass mode, including safety warnings.

Chapter 6 Operator Control and Display Panel

Alarm List

Provides a comprehensive list of UPS events and their explanations.

Chapter 7 Maintenance

Maintenance Operation Precautions

Details precautions for maintenance engineers, including safety measurements.

Bypass Module Maintenance

Step-by-step instructions for maintaining the bypass module and related components.

Chapter 8 Product Specification

Applicable Standards and Compliance

Lists European and national standards the UPS design complies with.

Electrical Characteristics (Input, DC Link, Output)

Details electrical specifications for input rectifier, DC link, and inverter output.