Installation
True Online 6-20k UPS User Manual
11
5. INSTALLATION
The system should be installed and wired only by qualified electricians in accordance
with applicable safety regulations.
NOTICEUPS operation in sustained temperature outside the range of 15-25
°
C (59
°
-77
°
F)
reduces battery life.
5.1 Unpacking and Inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
1 UPS
1 user manual
2 connectorsred and whitefor battery with 4 contacts (6KL and 10KL)
2 cable entry protector (6K and 10K)
2) Inspect the appearance of the UPS to see if there is any damage during transportation.
Do not turn on the unit and notify the carrier and dealer immediately if there is any
damage or lacking of some parts.
5.2 Connect Input/Output Power
1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least
0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until the UPS is fully
dried inside out before proceeding installation and use. Otherwise there are hazards
of electric shock.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and
the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. Open the battery
breaker for long backup time model (“L” model).
1) Open the terminal block cover located on the rear panel of the UPS, please refer to
the appearance diagram.
2) For 6k(L) UPS, it is recommended to select the UL1015 10AWG(6mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output
wirings.
3) For 10k(L) UPS, it is recommended to select the UL1015 8AWG(10mm
2
) wire or

Questions and Answers: