Rated Parameters Set on LCD
True Online 6-20k UPS User Manual
35
6. Press “ENTER” button to confirm output voltage selection and activate frequency setting.
Press
to select the rated frequency. 50Hz and 60Hz are available for
selection.
7. Press “ENTER” button to confirm frequency selection, and the current parameters are
shown on LCD as below
8. Shutdown UPS completely and restart UPS to activate the setting. Enter in and
enter in system information to check if the rated setting has been activated as below