8.1 Technical data
8.1.1 General specifications
Detection 
method
Inxpect motion detection algorithm based 
on FMCW radar
Frequency Working band: 24–24.25 GHz
Transmission power: ≤ 13 dBm
Modulation: FMCW
Detection 
interval
From 0 to 4 m (from 0 to 13.1 ft), depending 
on the installation conditions.
Detectable 
target RCS
0.17 sqm
Field of view                                  l 110° (sensor horizontal plane: 110°, 
sensor vertical plane: 30°)
l 50° (sensor horizontal plane: 50°, 
sensor vertical plane: 15°)
Guaranteed 
response time
< 100 ms
Total 
consumption
12.2 W (control unit and six sensors)
Electrical 
protections
Polarity inversion
Overcurrent through resettable integrated 
fuse (max. 5 s @ 8 A)
Overvoltage 
category
II
Altitude Max 2000 m ASL
Air humidity Max 95%
Noise emission Negligible
8.1.2 Safety parameters
SIL (Safety 
Integrity Level)
2 
HFT 0
SC 2
TYPE B
PL (Performance 
Level)
d
ESPE Type (EN 
61496-1)
3
Category (EN 
ISO 13849)
3 for ISC-B01
2 for  ISC-B01, ISC-02 and ISC-03
Communication 
protocol 
(sensors-control 
unit)
CAN complies with standard EN 50325-5
Mission time 20 years
MTTFd 44 years
PFHd - category 
2
With PROFINET/PROFIsafe communication:
l Access detection: 4.60E-08  [1/h]
l Restart prevention: 4.60E-08  [1/h]
l Muting: 6.13E-09  [1/h]
l Stop signal: 6.14E-09  [1/h]
l Restart signal: 6.14E-09  [1/h]
Without PROFINET/PROFIsafe 
communication:
l Access detection: 4.50E-08  [1/h]
l Restart prevention: 4.50E-08  [1/h]
l Muting: 5.13E-09  [1/h]
l Stop signal: 5.14E-09  [1/h]
l Restart signal: 5.14E-09  [1/h]
PFHd - category 
3
With PROFINET/PROFIsafe communication:
l Access detection: 7.81E-09  [1/h]
l Restart prevention: 7.81E-09  [1/h]
l Muting: 6.13E-09  [1/h]
l Stop signal: 6.14E-09  [1/h]
l Restart signal: 6.14E-09  [1/h]
Without PROFINET/PROFIsafe 
communication:
l Access detection: 7.72E-08  [1/h]
l Restart prevention: 7.72E-08  [1/h]
l Muting: 5.13E-09  [1/h]
l Stop signal: 5.14E-09  [1/h]
l Restart signal: 5.14E-09  [1/h]
SFF 99.21%
DCavg 98.24%
MRT ** < 10 min
Safe state when 
a fault occurs
At least one OSSD is in OFF-state. Stop 
message sent on fieldbus (if available) or 
communication interrupted
Note*: the systematic capability is guaranteed only 
if the user uses the product according to the 
instructions of this manual and uses the product in 
the appropriate environment.
Note**: the MRT considered is the Technical Mean 
Repair Time, i.e. it takes in consideration 
availability of skilled personnel, adequate tools and 
spare parts. Considering the type of device, the MRT 
corresponds to the time necessary for the device 
replacement. 
8.1.3 Ethernet connection (if 
available)
Default IP 
address
192.168.0.20
Default TCP port 80
Default netmask 255.255.255.0
Default gateway 192.168.0.1
8.1.4 Control unit features
Outputs Configurable as follows:
l 4 Output Signal Switching Devices 
(OSSDs) (used as single channels)
l 2 dual channel safety outputs
l 1 dual channel safety output and 2 
Output Signal Switching Devices 
(OSSDs)
OSSD 
characteristic
l Maximum resistive load: 100 K Ω
l Minimum resistive load:70 Ω
l Maximum capacitive load: 1000 nF
l Minimum capacitive load:10 nF
Safety outputs High-side outputs (with extended 
protection function)
l Max current: 0.4 A
l Max power: 12 W
The OSSDs provide what follows:
l ON-state:from Uv-1V to Uv  (Uv = 24V 
+/- 4V)
l OFF-state:from 0 V to 2.5 V r.m.s.
Inputs 2 dual channel type 3 digital inputs with 
common GND
See "Voltage and current limits for digital 
inputs" on page90.