EasyManua.ls Logo

IPM balancedpower plus - Page 49

Default Icon
99 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION III
Operation
Page 3.18
BP+2.9X
11/95
Table 3.2 (continued)
Screen Message Description Corrective Action
inv bIn fusB Inverter fuse B blown Test/replace inverter fuses on A2 power
assembly.
inv bIn fusC Inverter fuse C blown Test/replace inverter fuses on A3 power
assembly.
inv PS fail Power supply failure Test/replace inverter drive boards on A1,
A2and A3 power assemblies.
inv PS norml* Power supply normal No action required
inv Iocked* lnverter phase locked No action required
inv not lock Inverter not phase locked Verify UPS input voltage and frequency.
inv ovr tmpA Inverter over temperature. phase
A
Verify cooling fans are operating on A1
power assembly.
inv ovr tmpB Inverter over temperature, phase
B
Verify cooling fans are operating on A2
power assembly.
inv ovr tmpC Inverter over temperature, phase
C
Verify cooling fans are operating on A3
power assembly.
inv norm tmp* Inverter temp. normal No action required
inv cur norm* Inverter current normal No action required
inv OC shtdn Inverter shut down -over current Remove some of the load
inv OT shtdn Inverter shut down -over
temperature
Room is too not or fan failure
inv cur limt Inverter current limit Reduce load on UF’S
xfer enabled* Transfer enabled No action required
Rexfr enabled* Retransfer enabled No action required
* Not an alarm condition.