SECTION III
Operation
Page 3.47
BP+2.9X
11/95
3.6 UPS Operating Procedures (continued)
3.6.3 UPS Maintenance Menu (continued)
3.6.3.5 Password Maintenance Menu (continued)
8. Press
to obtain this screen.
9. Press
to return to the Password
Maintenance Menu.
10. Depress
to return to Previous Menu.
11. Depress
to leave UPS Maintenance Menu.
3.6.4 System Shutdown
1. Perform the Bypass/Shutdown procedure (Paragraph 3.6.3.3).
NOTE: This leaves the critical load powered by the utility power source
through the bypass.
2. To remove all power to the load, open the BYPASS CIRCUIT BREAKER.
3.6.5.CPU Fault
If this message should appear on the
screen, the UPS is transferred to bypass. Call
Service Hotline at (800) 777-8922.