SECTION VII
Remote Video Terminal
Page 7.1
BP+2.9X
11/95
7.1 General
An optional remote video terminal, supplied by LorTec or by the customer, is
plugged into the optional RS232 communication or telephone modem port. If this
port was not purchased, this section does not apply to your UPS.
The remote monitor is to be a video display terminal capable of emulating a
VT100 or equivalent.
7.2 RS232 Interlace
When COM1 or COM2 user interface is selected, the basic CRT Menu
Screen looks like this during normal UPS operation. A valid password must be
entered to access this screen.
[*] UPS Normal [ ] Transferred to Bypass
[ ] AC Input Failure [ ] Transfer not Available
[ ] Low Battery Voltage [ ] Battery Not Available
[ ] UPS Overloaded [ ] Retransfer Inhibited
UPS Maintenance Input Van 121.1 Link Voltage 400.1
Menu Input Vbn 121.8 Battery Amps -7.2
Input Vcn 121.0 Max Out CF 1.86
UPS Input Ia 62.7 Output KW 0.0
Operating Input Ib 62.5 Output KVA 1.0
Normally Input Ic 62.6 Output PF 0.00
08/30/95 Bypass Vab 216.2 Output Van 120.1
10:07:01.314 Bypass Vbc 215.6 Output Vbn 120.3
ups normal Bypass Vca 224.7 Output Vcn 119.9
Input Vab 210.1 Input Freq 60.00 Output Ia 3.3
Input Vbc 209.2 Output Freq 60.00 Output Ib 3.3
Input Vca 210.4 Inlet Temp 19.9 Output Ic 3.3
[N]ext [P]revious [S]ilence [U]p [D]own [E]nter [^R]efresh [H]istory
The top segment represents the LED's on the front of the UPS monitor panel.
The four-column segment represents the messages which appear on the monitor
panel's message screen. (Numbers are typical; actual values will appear.)