EasyManua.ls Logo

Iskra MC350 - Starting Current for PF and PA (Ma) (MC350, MC350 H and MC330 Only); Starting Current for All Powers (Ma); Starting Voltage for All Powers; Starting Voltage for SYNC (MC350, MC350 H and MC330 Only)

Default Icon
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SETTINGS
2
6
Measuringcentres
MC320,MC330,MC350&MC350H‐User’sManua
l
Maximumdemand(MD)timeconstant(MC350,MC350HandMC330
only)
Theinstrumentprovidesmaximumdemandvaluesbasedonathermalfunction.Thermalfunctiontime
constantcanbeselectedviakeyboardorviacommunication.
MainmenuSettingsGeneralMDmode/MDtimeconstant
THERMALFUNCTION
Athermalfunctionassuresexponentthermalcharacteristicbasedonsimulationofbimetalmeters.
Maximalvaluesandtimeoftheiroccurrencearestoredindevice.Atimeconstant(t.c.)canbesetfrom1to255
minutesandis6−methermalmeconstant(t.c.=6*thermalmeconstant).
Example:
Mode:Thermalfunction
Timeconstant:8min.
CurrentMDandmaximalMD:Resetat0min.
StartingcurrentforPFandPA(mA)(MC350,MC350HandMC330only)
Atallmeasuringinputsnoiseisusuallypresent.Itisconstantanditsinfluenceontheaccuracyisincreasedby
decreasingmeasuringsignals.Itispresentalsowhenmeasuringsignalsarenotconnectedanditoccursatall
furthercalculationsasverysporadicmeasurements.Bysettingacommonstartingcurrent,alimitofinputsignal
isdefinedwheremeasurementsandallothercalculationsarestillperformed.
Startingcurrentforallpowers(mA)
Noiseislimitedwithastartingcurrentalsoatmeasurementsandcalculationsofpowers.
Startingvoltageforallpowers
Noiseislimitedwithastartingvoltagealsoatmeasurementsandcalculationsofpowers.Untilvoltagereaches
userdefinedstartingvoltagelimit,allpowersaresetto0.Usingthreewireelectricalconnections,virtualphase
voltageisusedincalculations.
StartingvoltageforSYNC(MC350,MC350HandMC330only)
IfallvoltagesarelessthanStartingvoltageforSYNC,thanthecurrentinputsareusedforsynchronisation.Ifall
currentsarelessthanStartingcurrentforPFandPA,thanthesynchronisationisstoppedandthefrequency
resultis0Hz

Thermal function
01234567891011121314151617181920
Time [min.]
Measured value
Present MD MD peak Input