Lock Wiring, using PoE:
The Pure IP Reader-Controller supports a simplified configuration when PoE is being used to supply
the lock’s power.
1.
Connect the Red wire on the ISONAS Reader-controller to the positive lead of the
electric lock. See Figure 7
2.
Connect the negative lead of the lock to the black wire on the ISONAS reader-
controller.
3.
See this manual’s “Managing Inductive Load Challenges“ section for more info regarding
the use of the BackEMF diode.
Figure 7