INSTALLATION
Mounting the inverter
The location where the inverter is to be mounted must be:
Dry: Do not allow any liquids to drip or splash onto the unit.
Cool: Do not install in direct sunlight or close to any heat sources,
the ideal ambient air temperature is between 15°C to 25°C.
Ventilated: Allow at least 60mm of clearance around the inverter
to allow adequate air flow, and make sure that the fans and vent
holes are not obstructed.
Safe: Do not install the inverter in the same compartment as the
batteries (only applies to Lead Acid, AGM, Gel and Sealed Lead
Acid) to prevent corrosion, or in any compartments where
flammable liquids or fumes may be or may become present.
Clean: Do not install the inverter in a dusty environment, as the
inverter contains cooling fans, any dust present will be sucked
into the inverter which may damage or shorten the life of the
inverter.
Close to batteries: Avoid excessive cable lengths as this will cause
voltage drop and lowers the performance of the inverter.
Fused: A fuse must be installed between the battery and the
inverter.