1) None of the electrics work.
A) The machine is not plugged in.
B) The line fuse has blown.
C) The current line is wrongly
connected in the junction box.
D) The cut off micro-switch is faulty or
wrongly adjusted.
D) Check, adjust or change.
E) Safety pressure switch faulty.
2) All the electrics work except
compressor.
A) Check switch installed in electrical
panel.
3) All the electrics work but the
compressor “klixons”
C) Obstruction in air circulation.
C) Move machine to a correct position.
E) Starter capacitor faulty.
F) Fan pressure swtich faulty or
wrongly
adjusted.
F) Replace or adjust pressure switch
G) Water pressure switch valve
faulty or
wrongly adjusted.
H) Cooling water pressure switch is
faulty
or badly adjusted.
J) Non-condensable gases in system.
4) Everything appears to be
running correctly but no ice is
being made in
the
evaporator.
A) Check overflow, water bin for leaks,
water entry valve and prime the
pump.
B) Faulty pump. B) Replace.
C) Water does not enter into the bin.
C) Check water entry valve and change
if is necessary.
D) There is water in the gas circuit. D) Replace the drier, empty the
refrigerant (vacuum) and charge
new refrigerant.
E) Check overflow pipe and for leaks.
Inspect draining valve in machines
with automatic cleaning system.
Check the buoy valve mechanism
in DP90 and DP140.
F) Freezing system is faulty (dirty
condenser, water pressure switch
or
entrance valve faulty or
wrongly
adjusted insufficient
refrigerant.
F) Clean condenser, check all the
system components: pressure
switch,
water inlet valve, refrigerant
charge,
etc.