Name
Setting Range
Setting
increments
Minimum
Initial
value
Parameters
0.1 0.0
BasicFunction
P110
V/Fbasefrequency
V/Fintermediatefrequen
cy~max.
frequency
P111
V/Fintermediate
voltage
V/F minimum voltage
~ V/F
maximumvoltage
0.1
Changing
P112
V/Fintermediate
frequency
V/Fminimumfrequency
~V/Fbase
frequency
0.01
2.50
P113
V/Fminirmimvoltage
0~V/Fintermediate
voltage
0.1 15.0
P114
V/Fminirmim
frequency
0~V/Fintermediate
frequency
P115 Carrierfrequency
P116
Automaticcarrier
lineup
Reserved
P117
Initializationof
parameters
8:InitializationofFactory
Setting
P118
Parameterlock
0:Unlockparameters
1:Lockupparameters
P200
Startmodeselection
0:regularstart
1:restartafterinspection
P201
Stopmodeselection
0:decelerationtoastop
1:coasting
P202 Startingfrequency
0.10~10.00Hz
P203 Stoppingfrequency
0.10~10.00Hz
P204
DCinjectionbrake
operationcurrent
(start)
0~150%ratedmotor
current
1.0K~15.0K
1
1
1
1
1
0.01
0.01
1%
0
0
0
0
0
0.5
0.5
50%
1.2
Changing
0.1
0.1
P205
DCinjectionbrake
operationtime(start)
0~25.0S
0.1
0
P206
DCinjectionbrake
operationcurrent
(stop)
0~150%ratedmotor
current
1%
60%
P207
DCinjectionbrake
operationtime(stop)
0~25.0S
0.1
0
P208
Torqueboost
0~20.0%
1
0%
P209
Ratedmotorvoltage
0~500.0V
Changing
0.1
P210
Ratedmotorcurrent
0~currentofsystem
Changing
0.1
5
Chapter 5 Function Parameters Table
FC100 Series User Manaul

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Janson Controls FC100-4T-4.0G and is the answer not in the manual?

Janson Controls FC100-4T-4.0G Specifications

General IconGeneral
BrandJanson Controls
ModelFC100-4T-4.0G
CategoryController
LanguageEnglish

Related product manuals