Differential Pressure Transducer Multi-Range
DP150 Series Installation Guide
Introduction
The Johnson Controls
®
DP150 Series senses differential
pressure over a multi-sense range. Every DP150
transducer is calibrated and tested before shipment to
guarantee performance for all pressure ranges. The DP150
is available in four versions that have field-selectable
range capability through slide switch and jumpers. See
Table 1. Units are either in inches (in.) of water column
(WC) or Pascal (Pa)
Figure 1: DP150 Transducer
Table 1: DP150 Multi-Sense range specifications
Product
code
Range UNI range BI range
A 1.0 in. WC ±1.0 in. WC
B 0.5 in. WC ±0.5 in. WC
C 0.25 in. WC ±0.25 in. WC
D 0.1 in. WC ±0.1 in. WC
E 250 Pa ±250 Pa
F 100 Pa ±100 Pa
G 50 Pa ±50 Pa
DP150MR1
H 25 Pa ±25 Pa
Table 1: DP150 Multi-Sense range specifications
Product
code
Range UNI range BI range
A 10.0 in. WC ±10.0 in. WC
B 5.0 in. WC ±5.0 in. WC
C 2.5 in. WC ±2.5 in. WC
D 1.0 in. WC ±1.0 in. WC
E 2500 Pa ±2500 Pa
F 1000 Pa ±1000 Pa
G 500 Pa ±500 Pa
DP150MR2
H 250 Pa ±250 Pa
A 5.0 in. WC ±5.0 in. WC
B 2.5 in. WC ±2.5 in. WC
C 1.0 in. WC ±1.0 in. WC
D 0.5 in. WC ±0.5 in. WC
E 1000 Pa ±1000 Pa
F 500 Pa ±500 Pa
G 250 Pa ±250 Pa
DP150MRG
H 100 Pa ±100 Pa
A 0.25 in. WC ±0.25 in. WC
B 0.1 in. WC ±0.1 in. WC
E 50 Pa ±50 Pa
DP150MRC
F 25 Pa ±25 Pa
*241148600020-*
Part No. 24-11486-00020 Rev. —