2.3 General Data
Category Mini VRF Outdoor Unit
Model (H,Y,C)VAHP036B21S (H,Y,C)VAHP048B21S (H,Y,C)VAHP060B21S
Power Supply 208/230V/ 1PH 60Hz 208/230V/ 1PH 60Hz 208/230V/ 1PH 60Hz
Cooling Capacity (Nominal) Btu/h (kW) 36,000 (10.6) 48,000 (14.1) 60,000 (17.6)
Power Input kW 2.53 3.78 5.05
Current Input A (208V/230V) 12.3 / 11.1 18.6 / 16.9 24.8 / 22.4
Heating Capacity (Nominal) Btu/h (kW) 40,000 (11.7) 54,000 (15.8) 64,000 (18.8)
Power Input kW 2.36 3.95 4.42
Current Input A (208V/230V) 11.8 / 10.6 19.6 / 17.7 21.7 / 19.6
Rated Capacity Btu/h 36,000 / 36,000 48,000 / 48,000 60,000 / 55,000
EER Btu/Wh 16.70 / 13.80 16.70 / 13.10 12.20 / 9.70
SEER Btu/Wh 23.50 / 18.70 24.10 / 18.40 16.80 / 15.90
Rated Capacity Btu/h 40,000 / 40,000 54,000 / 54,000 64,000 / 64,000
COP W/W 5.12 / 3.90 4.56 / 3.86 3.90 / 3.30
HSPF Btu/Wh 12.80 / 11.00 11.70 / 11.80 12.10 / 10.60
Indoor
o
F WB (
o
C WB)
59 (15) ~ 73 (23) 59 (15) ~ 73 (23) 59 (15) ~ 73 (23)
Outdoor
o
F DB (
o
C DB)
23 (-5) ~ 118 (48) *3 23 (-5) ~ 118 (48) *3 23 (-5) ~ 118 (48) *3
Indoor
o
F DB (
o
C DB)
59 (15) ~ 80 (27) 59 (15) ~ 80 (27) 59 (15) ~ 80 (27)
Outdoor
o
F WB (
o
C WB)
-4 (-20) ~ 59 (15) *4 -4 (-20) ~ 59 (15) *4 -4 (-20) ~ 59 (15) *4
Cabinet Color (Munsell Code) - 1.0Y8.5/0.5 1.0Y8.5/0.5 1.0Y8.5/0.5
Height in. (mm) 54-5/16 (1380) 54-5/16 (1380) 54-5/16 (1380)
Width in. (mm) 37-3/8 (950) 37-3/8 (950) 37-3/8 (950)
Depth in. (mm) 14-9/16 (370) 14-9/16 (370) 14-9/16 (370)
Height in. (mm) 59-9/16 (1513) 59-9/16 (1513) 59-9/16 (1513)
Width in. (mm) 40-3/8 (1025) 40-3/8 (1025) 40-3/8 (1025)
Depth in. (mm) 18-1/8 (460) 18-1/8 (460) 18-1/8 (460)
Net lbs (kg) 249 (113) 249 (113) 249 (113)
Gross lbs (kg) 267 (121) 267 (121) 267 (121)
Total Indoor Unit Capacity % 130-60 130-60 105-60
Max. Indoor Units/System - 6 8 8
Type -
Multi-Pass Cross-
Finned Tube
Multi-Pass Cross-
Finned Tube
Multi-Pass Cross-
Finned Tube
Material - Cu-Al (Anti-corrosion) Cu-Al (Anti-corrosion) Cu-Al (Anti-corrosion)
Type - HA36PHD-A1S2 HA36PHD-A1S2 HA36PHD-A1S2
Motor Phase / Pole - / - 3PH / 6 3PH / 6 3PH / 6
Start Method - Inverter Inverter Inverter
Operation Range % 10 ~ 100 10 ~ 100 10 ~ 100
Refrigeration Oil Type - FVC68D FVC68D FVC68D
Crank Case Heater W × Qty 52W(208V) ×1 52W(208V) ×1 52W(208V) ×1
Type - Propeller Fan Propeller Fan Propeller Fan
Quantity Qty 2 2 2
Motor Output (Pole) W (Pole) 58(10) + 58(10) 58(10) + 58(10) 58(10) + 58(10)
Airflow Rate cfm
(m
3
/min)
3177 (90) 3530 (100) 3530 (100)
Drive - Direct-drive Direct-drive Direct-drive
Min. Circuit Amps A 31 31 31
Max. Overcurrent Protective Device A 40 40 40
Cooling (Night-Shift) dB (A) 51 (44) 52 (46) 53 (46)
Heating dB (A) 52 54 56
Cycle -
Compressor -
Fan Motor -
PCB (Control Circuit) -
Type - R410A R410A R410A
Charge Amount lbs (kg) 7.9 (3.6) 7.9 (3.6) 7.9 (3.6)
Refrigeration Oil Charge Amount gal/Unit (L/Unit) 0.34 (1.3) 0.34 (1.3) 0.34 (1.3)
Defrost Method - Reversed Refrigerant Cycle Reversed Refrigerant Cycle Reversed Refrigerant Cycle
Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Fuse on PCB(5A)
Refrigerant
Main Refrigerant
Piping
High pressure switch
at 601psi (4.15MPa)
Over-current protection
Over-heat protection
Circuit Breaker (30A)
Over-current protection
Over-heat protection
Circuit Breaker (30A)
Over-current protection
Over-heat protection
Circuit Breaker (30A)
Over-current protection
Over-heat protection
Self-contained fuse (5A)
Over-current protection
Over-heat protection
Self-contained fuse (5A)
Over-current protection
Over-heat protection
Self-contained fuse (5A)
High pressure switch
at 601psi (4.15MPa)
Fuse on PCB(5A)
Fan
Electrical
Sound Pressure Level
*5
Protection Devices
High pressure switch
at 601psi (4.15MPa)
Fuse on PCB(5A)
Compressor
Capacity (Nominal) *1
Efficiency Ratings *2
(Non-Ducted / Ducted)
Cooling
Heating
Cooling Operating
Range
Heating Operating
Range
Outer Dimensions
Package Dimensions
Weight
Connection Ratio
Heat Exchanger
NOTES:
*1 Rating Conditions:
Cooling Heating
Indoor Air Inlet Temperature: 80
o
F (26.7
o
C) DB Indoor Air Inlet Temperature: 70
o
F (21.1
o
C) DB
67
o
F (19.4
o
C) WB Outdoor Air Inlet Temperature: 47
o
F (8.3
o
C) DB
Outdoor Air Inlet Temperature: 95
o
F (35.0
o
C) DB 43
o
F (6.1
o
C) WB
Piping Length: 24.6ft. (7.5m), Piping Lift: 0ft. (0m)
*2 Efciency ratings are based on the AHRI 210/240 test standard.
*3 There are some exceptions and notes for cooling operation ranges. For details, refer to Section 2.12 “Operation Range”.
*4 There are some exceptions and notes for heating operation ranges. For details, refer to Section 2.12 “Operation Range”.
*5 Measurement Point: 3.3ft. (1m) from the air outlet side, 4.9ft. (1.5m) from oor level.
The operation sound is measured in an anechoic chamber. However, the actual operation sound may appear louder or with an echo
because of surrounding environmental noise. Be sure to check environmental conditions before installation.
The sound of the air inlet side may be 3dB higher than that of the air outlet side.