Technical Bulletin—TC-9102 27
Specifications &
Technical Data
Supply Voltage
24 VAC, +15% to -10%, 50-60 Hz.
Power Consumption
3 VA for controller and room command module.
(Add power consumption of connected actuating devices.)
Ambient Operating
Conditions
0° to 50°C
10 to 90% RH noncondensing
Ambient Storage
Conditions
-20° to 70°C
10 to 90% RH noncondensing
Terminations
Screw terminal blocks for 1.5 mm
2
(maximum) cable.
Separable terminal blocks are available as an option.
Communication
Interfaces
Optically isolated RS-485 interface for N2 bus connection at 9600 baud.
Room Command Module (TM-9180) interface at 600 baud - non-isolated
synchronous bus.
Controller Addressing
0-255 selectable on DIP switches (6) and jumpers (2)
Inputs
Window Contact: Closed (<1 Kohm) = window closed
Occupancy Sensor: Closed (<1 Kohm) = occupied
Room Temperature Sensor: NTC Thermistor 0-40 °C*
Remote Set Point: 10 Kohm potentiometer*
3-Speed Fan Override: 10 Kohm potentiometer*
Occupancy Button: Momentary Contact*
*from Room Command Module TM-9150/9160/9170
Outputs
Heating/Cooling
Analog: 0-10 VDC, maximum 10 mA
DAT: Triac rated at 24 VAC, maximum 0.5 A*
PAT: 2 x triacs rated at 24 VAC, maximum 0.5 A*
2-Stage On/Off: 2 x triacs rated at 24 VAC, maximum 0.5 A*
* Maximum 1 mA current leakage
Fan Control
On/Off: Relay contact rated at 250 VAC, maximum 3A
3-Speed: Relay contact rated at 250 VAC, maximum 3A
Variable Fan Speed: 0-10 VDC, maximum 10mA
Mounting
DIN rail or surface (two brackets supplied with controller).
Dimensions (H x W x D)
118 mm x 108 mm x 31 mm (standard terminals)
146 mm x 108 mm x 31 mm (separable terminals)
Housing
Material: ABS + polycarbonate, self-extinguishing UL94-VO
Protection: IP30 (IEC529)
Shipping Weight
0.3 kg
CE Compliance
Directive 89/336/EEC EN 50081-1, EN 50082-1
Directive 73/23/EEC EN 60730